Roof drainage calculates the roof runoff to DIN 1986-100 and EN 12056-3. Area, runoff coefficient and rainfall give the flow, and the downpipe is the smallest suitable HT or SML nominal size.
Total
3,00
l/s
DN
70
HT
Verify buried pipes and emergency overflows separately per DIN 1986-100.
Roof
Check values against DIN 1986-100 Table 9.
Take local rainfall values from KOSTRA-DWD.
Pipe
Save in —
Roof drainage follows DIN 1986-100 and EN 12056-3. Discharge is Q = r(5,2) · C · A / 10 000 in l/s, with the horizontal roof area A and the runoff coefficient C. The emergency overflow is Qnot = (r(5,100) − r(5,2) · C) · A / 10 000. The downpipe is sized with Wyly–Eaton: Q = 2.5·10⁻⁴ · kb^(−1/6) · di^(8/3) · f^(5/3), with kb = 0.25 mm and a degree of fill f = 0.33. The smallest HT or SML nominal size whose bore carries the share per downpipe is chosen.
100 m², C = 1.0, r(5,2) = 300 l/(s·ha), r(5,100) = 600, one HT downpipe: Q 3.00 l/s, DN 70, capacity 3.82 l/s, emergency overflow 3.00 l/s.