Plumbing
Discharge
2,00l/s
DN
100
Velocity
0,65m/s
Drainage finds the waste-water discharge to DIN EN 12056-2. Fixture units and the frequency factor give the volume flow. Nominal size is then chosen together with the gradient and the pipe material.
Discharge
2,00
l/s
Nominal size
100
DN
Operating roughness kb = 1.0 mm (DIN 1986-100) Material k = 0,10 mm, reference only. Part fill h/d = 0.5.
Input
Pipe section
Pipe
Use
Washbasin
DU 0,5 · min. DN 40
Shower
DU 0,6 · min. DN 50
Shower with plug
DU 0,8 · min. DN 50
Bath
DU 0,8 · min. DN 50
Kitchen sink
DU 0,8 · min. DN 50
Dishwasher
DU 0,8 · min. DN 50
Washing machine
DU 0,8 · min. DN 50
WC 6 litre
DU 2,0 · min. DN 100
Urinal (flush valve)
DU 0,5 · min. DN 50
Urinal (cistern)
DU 0,8 · min. DN 50
Floor drain DN 50
DU 0,8 · min. DN 50
Save in —
Waste-water discharge follows DIN EN 12056-2: Qww = K times the square root of the sum of fixture units, at least the largest single unit, plus a continuous flow. A branch and a collecting pipe inside the building are sized at a part fill of h/d = 0.5, and a buried pipe outside at h/d = 0.7. The calculation is Colebrook-White with the operating roughness kb = 1.0 mm for every material. A stack uses the allowed flows of Table 11 for main ventilation, not the part-fill formula. The minimum nominal size of the largest fixture still applies.
HT DN 100, 1% gradient, half full: limit 3.10 l/s. The same pipe at h/d = 0.7 carries 5.19 l/s. A stack at 2.20 l/s needs DN 90 with Qmax 2.7 l/s.