The psychrometric chart finds the state of moist air from temperature, humidity and pressure using the Magnus formula. It shows humidity ratio, enthalpy, dew point, density and specific volume. Heating, cooling and mixing can be read as air processes.
x
7,37
g/kg
h
51,1
kJ/kg
Heat
1,67
kW
1Heating
Process
1013 hPa
Save in —
The psychrometric chart finds moist air with the Magnus formula for saturation vapour pressure. Temperature, relative humidity and pressure give humidity ratio, enthalpy, dew point, wet-bulb temperature, density and specific volume. Heating and cooling keep the humidity ratio until the saturation line is reached. Mixing is the mass balance of both streams. The limits are about −40 to 95 °C and 700 to 1,200 hPa.
22 °C and 45% at 101,325 Pa: humidity ratio 7.37 g/kg, enthalpy 40.9 kJ/kg, dew point 9.5 °C.