Heating
Head
0,22m
Pressure
21,0mbar
Velocity
0,44m/s
Pressure drop calculates friction and local losses of a heating run. Pipe friction follows Darcy–Weisbach, and fittings enter as the sum of zeta values. Pressure loss and pump head for selecting the pump come from that.
Pump head
0,22
m
with 15%
0,25
m
k = 0,0015 mm
Pipe
Save in —
The pressure drop of a heating run is pipe friction plus local losses. Friction follows Darcy–Weisbach with Colebrook-White, and the fittings are the sum of the ζ values times the dynamic pressure. Pump head is that pressure divided by density and gravity. A 15% allowance is shown only as a note for selecting the pump, not inside the physics. ζ may be zero, an empty field may not.
Copper DN 20, 400 l/h, 60 °C, 12 m, sum of ζ = 2.5: 11.8 mbar, which is 0.12 m of pump head.