Cross-trade
Conlit fire collar
116 / 157mm inside / outside
Penetration sizing picks the bore and the fire-stopping product for one pipe. Shell or collar follow the outside diameter, the material and the building element. The result is one product and one core hole, not a fire-resistance calculation.
Conlit fire collar
116 / 157
mm inside / outside
Collar on the pipe, not as a shell in the bore. Annular gap around the pipe about 4 mm PE strip, the rest with mortar. Do not drill the collar outside diameter.
Open sourceElement
Service
Nominal size
In the penetration
Save in —
Penetration sizing matches one pipe to a fire-stopping product and the bore that goes with it. Metal services get a Conlit shell or Missel insulation, and combustible or drainage pipes get a collar. The choice follows the outside diameter, the building element and whether the hole is already drilled. A fire-resistance time is not calculated. The product approval remains decisive, not this selection.
SML DN 100, 110 mm outside, 200 mm wall: Conlit 150 U, Bore 180 mm, shell 110 × 35.